Imagine your favorite movie. Now imagine the screening stops at 2 a.m. because the labeler ran out of labels. There’s no one onsite, and by morning, the remaining plates have been waiting for hours.

Most automated processes that fail overnight do so for mundane reasons, such as consumables, heated devices not reaching temperature, or an out-of-range incubator. In laboratory robotics and automation, the problem is rarely the robot itself; it is typically equipment that was overlooked before heading home for the night.

Genera, the scheduling software from Retisoft Inc., lets a process poll each instrument to see whether it’s ready to accept samples.

The instrument command node, introduced in version 7 of Genera, executes any command a driver exposes within the context of a process. Quality control becomes part of your laboratory workflow automation, not a sticky note on the back of a device. These checks are one piece of how Genera turns existing lab instruments into one scheduled system.

People Also Ask

What are lab automation instrument checks?

They are questions a process asks the instruments it uses before or during a run, such as whether a seal is in place or what an incubator’s temperature is. The process then continues or pauses based on the answer.

How does genera check an instrument during a process?

The instrument command node runs a driver command and saves the result in a variable. Then a decision node compares the value to a limit you choose.

Do quality checks slow down an automated run?

Not if they run only once. A quick script ensures checks run only on the first batch, and the operator can turn them on or off when scheduling.

1. Seal Consumables Remaining

In this scenario, one of the Retisoft process quality checks sees an instrument command that gets the instrument’s plate peeler to report the remaining number and save it in a variable; then a decision node compares that variable to a threshold value of 5. If it is below 5, you will see a message from Genera asking you to add some seals and click OK, which is what happened in this demo when the instrument reported 350.

2. Labels Remaining In The Labeler

The same operation is also used in the same demo, but on the labeler itself, reporting how many labels are left to use, with the same message appearing if fewer than 3 are left.

3. Incubator Temperature Inside A Range

A single threshold check can allow you to specify a range by using a script in the decision node to check that the value is between 30 and 40 degrees, which, in the case of the incubator, it was (37), so no message appeared. This script could also check other values, such as humidity or CO2.

4. Tip Counts In The Boxes On Deck

Genera tracks how many tips are in use as a property of the tip box definition. So, for a full tip box, that might be 96. After every protocol on the automated liquid handler, a small script decrements the number of tips by those just used and updates the value. In Retisoft’s example, because each plate used 32 tips, one tip box was used for every three plates. At zero, a decision node marks the tip box as empty, sends it back to the hotel, and gets a new one from the deck.

The catch here is that while the number is tracked in software, it’s not on a sensor. Make sure you’re loading full tip boxes and noting them as such, or the model will drift from reality. Tracking consumables in software is one way automation software reduces error in life science research.

5. Whether The Right Labware Is Even Present

Finally, labware nodes act as filters. If no plate meets the criteria, say, a plate that has operational status of read ready, Genera will continue waiting and not move any plates until one does arrive. Script criteria can further narrow down the search by property, partial barcode, or status. A decision node using the location will check whether a tip box already exists in a nest before getting another one.

6. Whether A Heated Device Has Reached Temperature

A plate coming under a cold sealer will emerge as a cross-contaminated mess. A start handler activates the sealer heater and sets a target temperature as the run begins. As the Retisoft engineers also note, a handler can hold up the process until the sealer announces it has reached the target temperature, so a plate cannot arrive at the device too early.

7. Instrument States Before The First Move

A start handler initializes all instruments in the preceding process, and a finish handler shuts them down afterward. For greater specificity, you can insert an instrument command in a decision node to verify a certain state, such as whether a shuttle is open or shut, before proceeding. A loop node lets you repeat the same command until a condition is met.

Running The Checks Once Rather Than Every Batch

Checking a sealer before every plate wastes time. In Retisoft’s ELISA example, the checks sit in a quality control lane with a decision node. A two-condition script returns true only on the first batch, where the batch index equals zero. The checks live in a subprocess, called once, then the assay continues. Reusing a subprocess this way is part of how Genera takes over repetitive scheduling tasks.

Letting The User Decide Whether To Check

The second condition in the script is a parameter variable. At a scheduled time, the operator sets quality control to true or false. A routine rerun skips the checks. A run after a weekend or a consumable change includes them.

Scheduling Checks For Monday Morning And Friday Night

Lab automation instrument checks can also be scheduled to run automatically. Genera recurrence acts like a calendar invite, scheduling a quality control process to occur weekly on Monday mornings and Friday evenings and ending the series after a specific number of runs, on a specific date, or never. Genera must be open at the scheduled check time for each run to begin.

What Happens At Two In The Morning Without Them

In an active robotics and automation lab, a suspended overnight run has more at risk than reagents. Plates sit idle, someone drives in, and the next day’s schedule is compromised. Without checks, the first notification of an issue is an interrupted run. With checks, the first notification is at 6 p.m., while someone is still in the building. Early warnings like this show why scheduling software keeps shared lab time productive.

Pair overnight or weekend runs with an error handler that sends email, Microsoft Teams, or Slack notifications, so the right person still gets the process, batch, and error when checks miss something.

Go Home Confident Your Overnight Run Will Finish

With seven checks and a little setup, the overnight run stops depending on luck. Genera turns each instrument into a source of answers: how many labels remain, whether the incubator sits in range, whether the sealer is hot. The process decides what happens next.

Retisoft Inc. configures Genera as device-agnostic software that works with the lab equipment you already own, from sealers and labelers to liquid handlers. If your team still checks consumables by hand before leaving, a Genera demo shows how these checks fit your own workflow.

Frequently Asked Questions

Which instrument commands does genera support?

Any command the instrument driver exposes. Since Genera 7, the instrument command node runs these commands inside a process, not only from the instrument control panel.

Does Genera physically count tips?

No. Genera tracks tip counts as a labware property and updates them by script after each protocol. Accurate counts depend on recording full boxes correctly at loading.

Do I need scripting for these checks?

Simple thresholds use built-in decision node conditions. Ranges and multi-condition checks, such as running on the first batch only, use a few lines of script.

Where do quality check results appear?

Returned values appear under variables in the task details. Decision nodes trigger operator messages whenever a value falls outside its limit.

Will an alert reach me if a check fails overnight?

Yes, with an error handler in place. Genera sends email, Microsoft Teams or Slack messages. The Teams and Slack programs are available from Retisoft support on request.